§ 5-5. Specific amendments to 2015 International Fire Code.  


Latest version.
  • [Specific amendments:]

    (1)

    102.1 Existing Structures - Construction and Design Provisions:

    Amend: Section 102.1 ; change #3 to read as follows:

    3. Existing structures, facilities, and conditions when required in Chapter 11 or in specific sections of this code.

    Add:

    (5) Additions, Alterations, Renovations;

    (a) Any addition, renovation, remodel that adds square footage to a building, such structure is now subject to all fire protection requirements as though it were new construction.

    (b) Any alteration or renovation that changes the occupancy floorplan or increases the occupancy load of the structure is now subject to all fire protection requirements as though it were new construction.

    (c) Any renovation or remodel that does not change the occupancy floorplan, occupancy classification, or increase the occupancy load of the structure shall be considered pre-existing compliant from having to meet fire current fire protection requirements for new construction.

    (2)

    105.1.1 Permits Required: Replace - "Fire Code Official" with "Community Services Department upon approval of the Fire Code Official".

    (3)

    Section 105.3.3 ; change to read as follows:

    105.3.3 Occupancy Prohibited before Approval. The building or structure shall not be occupied prior to the fire code official issuing a permit when required and conducting associated inspections indicating the applicable provisions of this code have been met.

    (4)

    105.4.1.1a Examination of Documents: Add - The Fire Code Official is authorized to require a third party review on submittals and documents. The third party reviewer shall be pre-approved by the Fire Code Official. All fees for the third party review shall be the responsibility of the submitter.

    (5)

    105.4.6a Retention of Construction Documents ; add the following sentence:

    Prior to issuance of a Certificate of Occupancy one set of "as built" drawings shall be provided to the Fire Code Official on electronic compact disc in an approved format.

    (6)

    Section 105.7 ; add Section 105.7.19 to read as follows:

    105.7.19 Electronic access control systems. Construction permits are required for the installation or modification of an electronic access control system, as specified in Chapter 10. A separate construction permit is required for the installation or modification of a fire alarm system that may be connected to the access control system. Maintenance performed in accordance with this code is not considered a modification and does not require a permit.

    (7)

    202 General Definitions ; Add

    [B] AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing, or similar care on a less than 24-hour basis to persons who are rendered incapable of self-preservation by the services provided. This group may include but not be limited to the following:

    - Dialysis centers

    - Procedures involving sedation

    - Sedation dentistry

    - Surgery centers

    - Colonic centers

    - Psychiatric centers

    {Remainder unchanged.}

    [B] ATRIUM. An opening connecting three or more stories... {remaining text unchanged}

    [B] DEFEND IN PLACE. A method of emergency response that engages building components and trained staff to provide occupant safety during an emergency. Emergency response involves remaining in place, relocating within the building, or both, without evacuating the building.

    FIRE WATCH. A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more qualified individuals or standby personnel when required by the fire code official, for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the fire department.

    FIREWORKS. Any composition or device for the purpose of producing a visible or an audible effect for entertainment purposes by combustion, deflagration, detonation, and/or activated by ignition with a match or other heat producing device that meets the definition of 1.4G fireworks or 1.3G fireworks as set forth herein. ... {Remainder unchanged.}

    HIGH-PILED COMBUSTIBLE STORAGE: add a second paragraph to read as follows:

    Any building classified as a group S Occupancy or Speculative Building exceeding 6,000 sq. ft. that has a clear height in excess of 14 feet, making it possible to be used for storage in excess of 12 feet, shall be considered to be high-piled storage. When a specific product cannot be identified, a fire protection system and life safety features shall be installed as for Class IV commodities, to the maximum pile height.

    HIGH RISE BUILDING. A building having any floors used for human occupancy located more than 55 feet above the lowest level of fire department vehicle access.

    REPAIR GARAGE. A building, structure or portion thereof used for servicing or repairing motor vehicles. This occupancy shall also include garages involved in minor repair, modification and servicing of motor vehicles for items such as lube changes, inspections, windshield repair or replacement, shocks, minor part replacement, and other such minor repairs.

    [BG] RESIDENTIAL GROUP R ; amend as follows:

    [BG] Residential Group R-1. Residential Group R-1 occupancies containing sleeping units where the occupants are primarily transient in nature, including:

    Boarding Houses (transient)

    Hotels (transient)

    Motels (transient)

    Short Term Rentals

    Congregate living facilities (transient) with 10 or fewer occupants are permitted to comply with the construction requirements for Group R-3.

    SELF-SERVICE STORAGE FACILITY. Real property designed and used for the purpose of renting or leasing individual storage spaces to customers for the purpose of storing and removing personal property on a self-service basis.

    SHORT TERM RENTAL (STR). The rental of a room, loft, or entire home for 30 to 180 days per calendar year to transient guests who have paid for accommodations.

    STANDBY PERSONNEL. Qualified fire service personnel, approved by the Fire Chief. When utilized, the number required shall be as directed by the Fire Chief. Charges for utilization shall be as normally calculated by the jurisdiction.

    UPGRADED OR REPLACED FIRE ALARM SYSTEM. A fire alarm system that is upgraded or replaced includes, but is not limited to the following:

    • Replacing one single board or fire alarm control unit component with a newer model

    • Installing a new fire alarm control unit in addition to or in place of an existing one

    • Conversion from a horn system to an emergency voice/alarm communication system

    • Conversion from a conventional system to one that utilizes addressable or analog devices

    The following are not considered an upgrade or replacement:

    • Firmware updates

    • Software updates

    • Replacing boards of the same model with chips utilizing the same or newer firmware

    (8)

    304.3.5 Waste Oil Containers ; Add the following:
    Only approved containers designed for the collection and disposal of waste cooking or motor oil may be used. For purposes of this section, 55-gallon drums are not considered approved containers. Existing occupancies using non-approved containers shall have 90 days to comply upon notification of this requirement.

    (9)

    307.1a Any outdoor burning shall be conducted in accordance with the "City of Gainesville Open Burning, Recreational Fires and Bonfires Regulations as follows:

    CITY OF GAINESVILLE, TEXAS: OPEN BURNING, RECREATIONAL FIRES, AND BONFIRES REGULATIONS

    This information is provided for all persons within the City Limits of Gainesville, Texas.

    Persons wishing to conduct an outdoor burn should be aware of State and Local Regulations that apply to outdoor burning. State Requirements are addressed in a document entitled "Outdoor Burning in Texas", published by the Texas Commission on Environmental Quality, (formerly the Texas Natural Resources Conservation Commission). This information can be accessed online at www.tceq.state.tx.us and searching under available publications. Local requirements from the City of Gainesville are covered in the 2015 Edition of the International Fire Code, Section 307, as amended. Any of these regulations may apply to outdoor burns in Gainesville.

    The Fire Code requires that all persons who wish to conduct open burning complete a permit application and obtain a burning permit. Before a permit is issued, a Fire Marshal's Office official may inspect the premises to verify information regarding the permit application. In instances where laws or regulations are enforceable by any other governmental entity having jurisdiction, joint approval shall be obtained. Permits shall be kept on the premises designated therein at all times and shall be posted in a conspicuous location on the premises, or shall be kept on the premises in a location designated by the Fire Marshal's office. Permits shall be subject to inspection at all times by an officer of the fire or police department or other persons authorized by the Fire Marshal. Permits may be revoked at any time when it is determined by the Fire Marshal (or designee) that any conditions or limitations set forth in a permit have been violated, which may result in fines or additional fees issued by the fire department or TCEQ.

    The authority to conduct outdoor burning under the regulations listed below does not exempt or excuse any person responsible from the consequences, damages, or injuries resulting from the burning and does not exempt or excuse anyone from complying with all other applicable laws or ordinances, regulations, and orders of governmental entities having jurisdiction, even though the burning is otherwise conducted in compliance with the regulations listed below.

    Review the following burn regulations and then contact the Community Services Department to request and/or apply for a burn permit. A Fire Inspector will set up an appointment to come out and conduct a site inspection. This inspection must be conducted with the owner or owner's representative. If the inspection passes, the Fire Inspector will approve the issuance of the permit and authorize the Community Services Department to issue the permit. It is recommended to apply for a burn permit two to three days prior to the desired commencement of the burn.

    A copy of the permit application and inspection must remain available on site at all times. Burning is allowed with a permit only after an on-site inspection by the Fire Marshal's Office. Permit fee is in accordance with the Fee Schedule adopted by the Gainesville City Council. Permits are issued "per occurrence". Burn permits are valid for 5 days. When the permit expires, applicants may start the permit process again.

    Contact police/fire dispatch non-emergency prior to the commencement of burning. Give the Dispatcher your address information, emergency call back telephone number and burn permit number. Also notify Fire Marshal's Office the weekday/business day before the planned burn to verify that the weather conditions are satisfactory to conduct the burn. The website www.accuweather.com will be utilized as a resource in making decisions on burn/no burn conditions and projections. The Fire Marshal's Office will also verify that a burn ban is not in effect. This approval will be recorded by the Fire Marshal's Office and could be considered a violation of the permit regulations if it is not made each day prior to commencement of an open burn.

    A phone shall be available to call 9-1-1 if the fire gets out of control.

    You must have control of your fire at all times. Out of control wildfires are subject to fees or fines to cover expenses incurred by the fire department during extinguishment.

    The location for open burning shall not be less than 300 feet from any structure, and provisions shall be made to prevent the fire from spreading to within 300 feet of any structure.

    Burning shall be commenced and conducted only when wind direction and other meteorological conditions are such that smoke and other pollutants will not cause adverse effects to any public roadway or off-site structure containing sensitive receptor(s) as listed below:

    • Winds more than 6 MPH but less than 15 MPH during the burn period.

    • Burning shall not be conducted during periods of actual or predicted persistent low-level atmospheric temperature inversions.

    The initiation of burning shall commence no earlier than one hour after sunrise. Burning shall be completed on the same day one hour before sunset (ceremonial and campfire/cooking fires may be later). In cases where residual fires and/or smoldering objects continue to emit smoke after this time, such areas shall be extinguished if the smoke from these areas has the potential to create a nuisance or traffic hazard condition. In no case shall the extent of the burn area be allowed to increase after this time.

    The burning of domestic waste is PROHIBITED. The State of Texas defines domestic waste as follows: wastes that normally result from the function of life within a residence—for example, kitchen garbage, untreated lumber, cardboard boxes, packaging, clothing, grass, leaves. Such things as tires, construction debris, furniture, carpet, electrical wire, and appliances are not considered to be domestic waste but shall not be burned. Other conditions of the general requirements for outdoor burning do not apply to the burning of domestic waste, but the outdoor burn must not cause a nuisance or traffic hazard. If at any time the burning causes or may tend to cause smoke to blow onto or across a roadway or highway, it is the responsibility of the person initiating the burn to post flag-persons on affected roads.

    Open burning shall be constantly attended by a person knowledgeable in the use of fire-extinguishing equipment and familiar with the permit limitations which restrict open burning until the fire is extinguished. An attendant shall supervise the burning material until the fire has been completely extinguished. A garden hose connected to a water supply or other approved fire-extinguishing equipment shall be readily available for use at open-burning sites.

    Burning must be conducted downwind of or at least 300 feet from any structure containing sensitive receptors located on adjacent properties unless prior written approval is obtained from whomever owns or rents the adjacent property and either resides or conducts business there.

    Recreational fires shall not be conducted within 100 feet of a structure, property line or combustible material. Conditions which could cause a fire to spread within 100 feet of a structure shall be eliminated prior to ignition. Recreational fires shall be limited to no larger than 3 feet in diameter and 2 feet in height.

    Bonfires or any other open burning shall be conducted utilizing standard open burning rules.

    If a complaint is received by Gainesville Fire-Rescue that your Outdoor Burn, Recreational Fire or Bonfire is aggravating the sensitive receptors i.e., eyes, nose, and/or lungs of persons in the area near your burn, you will be asked by the Fire Marshal or his representative to immediately extinguish the fire.

    Please contact the Fire Marshal's Office if you have any questions in reference to open burning or burn permits.

    Thank you for your compliance with these fire safety requirements.

    (10)

    Section 307.1.1 ; change to read as follows:

    307.1.1 Prohibited Open Burning. Open burning that is offensive or objectionable because of smoke emissions or when atmospheric conditions or local circumstances make such fires hazardous shall be prohibited.
    Exception: {No change.}

    (11)

    Section 307.2 ; change to read as follows:

    307.2 Permit Required. A permit shall be obtained from the fire code official in accordance with Section 105.6 prior to kindling a fire for recognized silvicultural or range or wildlife management practices, prevention or control of disease or pests, or open burning. Application for such approval shall only be presented by and permits issued to the owner of the land upon which the fire is to be kindled.

    Examples of state or local law, or regulations referenced elsewhere in this section may include but not be limited to the following:

    1. Texas Commission on Environmental Quality (TCEQ) guidelines and/or restrictions.

    2. State, County, or Local temporary or permanent bans on open burning.

    3. City of Gainesville, Texas: Open Burning, Recreational Fires, and Bonfires Regulations as established by this Code.

    (12)

    Section 307.3 ; change to read as follows:

    307.3 Extinguishment Authority. The fire code official is authorized to order the extinguishment by the permit holder, another person responsible or the fire department of open burning that creates or adds to a hazardous or objectionable situation.

    (13)

    Section 307.4 ; change to read as follows:

    307.4 Location. The location for open burning shall not be less than 300 feet (91,440 mm) from any structure, and provisions shall be made to prevent the fire from spreading to within 300 feet (91,440 mm) of any structure.

    Exceptions: {No change.}

    (14)

    307.4.3 Portable Outdoor Fireplaces: Add to the end of the sentence "...and shall comply with the requirements of Section 308.3.1."

    (15)

    Section 307.4.3 ; add the following clause to the end of the sentence:

    "... and shall comply with the requirements of Section 308.3.1."

    Exceptions: add exception #2 to read as follows:

    Exceptions:

    2. Where buildings, balconies and decks are protected by an approved automatic sprinkler system.

    (16)

    Section 307.4.4 and 5 ; add section 307.4.4 and 307.4.5 to read as follows:
    307.4.4 Permanent Outdoor Firepit. Permanently installed outdoor firepits for recreational fire purposes shall not be installed within 15 feet of a structure or combustible material.

    Exception: Permanently installed outdoor fireplaces constructed in accordance with the International Building Code.

    307.4.5 Trench Burns. Trench burns shall be conducted in air curtain trenches and in accordance with Section 307.2.

    (17)

    Section 307.5 ; change to read as follows:

    307.5 Attendance. Open burning, trench burns, bonfires, recreational fires, and use of portable outdoor fireplaces shall be constantly attended until the... {Remainder unchanged.}

    (18)

    Section 308.1.4 ; change to read as follows:

    308.1.4 Open-flame Cooking Devices. Open-flame cooking devices, charcoal grills and other similar devices used for cooking shall not be located or used on combustible balconies, decks, or within 10 feet (3048 mm) of combustible construction.

    Exceptions:

    1. One- and two-family dwellings, except that LP-gas containers are limited to a water capacity not greater than 50 pounds (22.68 kg) [nominal 20 pound (9.08 kg) LP-gas capacity] with an aggregate LP-gas capacity not to exceed 100 lbs (5 containers).

    2. Where buildings, balconies and decks are protected by an approved automatic sprinkler system, except that LP-gas containers are limited to a water capacity not greater than 50 pounds (22.68 kg) [nominal 20 pound (9.08 kg) LP-gas capacity], with an aggregate LP-gas capacity not to exceed 40 lbs (2 containers).

    3. {No change.}

    (19)

    Section 308.1.6.2, Exception #3 ; change to read as follows:

    Exceptions:

    3. Torches or flame-producing devices in accordance with Section 308.1.3.

    (20)

    Section 308.1.6.3 ; change to read as follows:

    308.1.6.3 Sky Lanterns. A person shall not release or cause to be released an unmanned free-floating devices containing an open flame or other heat source, such as but not limited to a sky lantern.

    (21)

    Section 311.5 ; change to read as follows:

    311.5 Placards. The fire code official is authorized to require marking of any vacant or abandoned buildings or structures determined to be unsafe pursuant to Section 110 of this code relating to structural or interior hazards,

    (22)

    Section 403.5 ; change Section 403.5 to read as follows:

    403.5 Group E Occupancies. An approved fire safety and evacuation plan in accordance with Section 404 shall be prepared and maintained for Group E occupancies and for buildings containing both a Group E occupancy and an atrium. A diagram depicting two evacuation routes shall be posted in a conspicuous location in each classroom. Group E occupancies shall also comply with Sections 403.5.1 through 403.5.3.

    (23)

    Section 404.2.2 ; add Number 4.10 to read as follows:

    4.10 Fire extinguishing system controls.

    (24)

    Section 405.4 ; change Section 405.4 to read as follows:

    405.4 Time. The fire code official may require an evacuation drill at any time. Drills shall be held at unexpected times and under varying conditions to simulate the unusual conditions that occur in case of fire.

    (25)

    Section 501.4 ; change to read as follows:

    501.4 Timing of Installation. When fire apparatus access roads or a water supply for fire protection is required to be installed for any structure or development, they shall be installed, tested, and approved prior to the time of which construction has progressed beyond completion of the foundation of any structure.

    (26)

    Section 503.1.1 ; add sentence to read as follows:

    Except for one- or two-family dwellings, the path of measurement shall be along a minimum of a ten feet (10') wide unobstructed pathway around the external walls of the structure.

    (27)

    Section 503.2.1 ; change to read as follows:

    503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 24 feet (7315 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 14 feet (4267 mm).

    Exception: Vertical clearance may be reduced; provided such reduction does not impair access by fire apparatus and approved signs are installed and maintained indicating the established vertical clearance when approved.

    (28)

    Section 503.2.2 ; change to read as follows:

    503.2.2 Authority . The fire code official shall have the authority to require an increase in the minimum access widths and vertical clearances where they are inadequate for fire or rescue operations.

    (29)

    503.2.3 Surface ; add the following sentence to the end of the paragraph:

    Refer to the most recently adopted subdivision regulations found within the City of Gainesville Code of Ordinances for the details and specifications for construction.

    (30)

    Section 503.3 ; change to read as follows:

    503.3 Marking. Striping, signs, or other markings, when approved by the fire code official, shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Striping, signs and other markings shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.

    (1) Striping - Fire apparatus access roads shall be continuously marked by painted lines of red traffic paint six inches (6") in width to show the boundaries of the lane. The words "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" shall appear in four inch (4") white letters at 25 feet intervals on the red border markings along both sides of the fire lanes. Where a curb is available, the striping North Central Texas Council of Governments 8 As of August 2015 IFC Amendments shall be on the vertical face of the curb.

    (2) Signs - Signs shall read "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" and shall be 12" wide and 18" high. Signs shall be painted on a white background with letters and borders in red, using not less than 2" lettering. Signs shall be permanently affixed to a stationary post and the bottom of the sign shall be six feet, six inches (6'6") above finished grade. Signs shall be spaced not more than fifty feet (50') apart along both sides of the fire lane. Signs may be installed on permanent buildings or walls or as approved by the Fire Chief.

    (30)

    Section 503.4 ; change to read as follows:

    503.4 Obstruction of Fire Apparatus Access Roads. Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The minimum widths and clearances established in Section 503.2.1 and any area marked as a fire lane as described in Section 503.3 shall be maintained at all times.

    (31)

    Section 505.1 ; change to read as follows:

    505.1 Address Identification . New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 6 inches (152.4 mm) high with a minimum stroke width of 1/2 inch (12.7 mm). Where required by the fire code official, address numbers shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road, buildings do not immediately front a street, and/or the building cannot be viewed from the public way, a monument, pole or other sign with approved 6 inch (152.4 mm) height building numerals or addresses and 4 inch (101.6 mm) height suite/apartment numerals of a color contrasting with the background of the building or other approved means shall be used to identify the structure. Numerals or addresses shall be posted on a minimum 20 inch (508 mm) by 30 inch (762 mm) background on border. Address identification shall be maintained.

    Exception: R-3 Single Family occupancies shall have approved numerals of a minimum 3 ½ inches (88.9 mm) in height and a color contrasting with the background clearly visible and legible from the street fronting the property and rear alleyway where such alleyway exists.

    (32)

    507.1 Required Water Supply ; add the following sentence:

    All installations in Section 507 shall conform to the most recently adopted subdivision regulations found in the City of Gainesville Code of Ordinances.

    (33)

    Section 507.5.4 ; change to read as follows:

    507.5.4 Obstruction. Unobstructed access to fire hydrants shall be maintained at all times. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants.

    (34)

    Section 509.1.2; add new Section 509.1.2 to read as follows:

    509.1.2 Sign Requirements. Unless more stringent requirements apply, lettering for signs required by this section shall have a minimum height of 2 inches (50.8 mm) when located inside a building and 4 inches (101.6 mm) when located outside, or as approved by the fire code official. The letters shall be of a color that contrasts with the background.

    (35)

    Section 603.3.2.1, Exception ; change exception to read as follows:

    Exception: The aggregate capacity limit shall be permitted to be increased to 3,000 gallons (11,356 L) in accordance with all requirements of Chapter 57. {Delete remainder of Exception.}

    (36)

    Section 603.3.2.2 ; change to read as follows:

    603.3.2.2 Restricted Use and Connection. Tanks installed in accordance with Section 603.3.2 shall be used only to supply fuel oil to fuel-burning equipment installed in accordance with Section 603.3.2.4. Connections between tanks and equipment supplied by such tanks shall be made using closed piping systems.

    (37)

    Section 604 ; change and add to read as follows:

    604.1.1 Stationary Generators. Stationary emergency and standby power generators required by this code shall be listed in accordance with UL 2200.

    604.1.2 Installation. Emergency power systems and standby power systems shall be installed in accordance with the International Building Code, NFPA 70, NFPA 110 and NFPA 111. Existing installations shall be maintained in accordance with the original approval, except as specified in Chapter 11.

    604.1.3 through 604.1.8 {No changes to these sections.}

    604.1.9 Critical Operations Power Systems (COPS). For Critical Operations Power Systems necessary to maintain continuous power supply to facilities or parts of facilities that require continuous North Central Texas Council of Governments 10 As of August 2015 IFC Amendments operation for the reasons of public safety, emergency management, national security, or business continuity, see NFPA 70.

    604.2 Where Required. Emergency and standby power systems shall be provided where required by Sections 604.2.1 through 604.2.24 or elsewhere identified in this code or any other referenced code.

    604.2.1 through 604.2.3 {No change.}

    604.2.4 Emergency Voice/alarm Communications Systems. Emergency power shall be provided for emergency voice/alarm communications systems in the following occupancies, or as specified elsewhere in this code, as required in Section 907.5.2.2.5. The system shall be capable of powering the required load for a duration of not less than 24 hours, as required in NFPA 72.

    Covered and Open Malls, Section 907.2.20 and 914.2.3
    Group A Occupancies, Sections 907.2.1 and 907.5.2.2.4
    Special Amusement Buildings, Section 907.2.12.3
    High-rise Buildings, Section 907.2.13
    Atriums, Section 907.2.14
    Deep Underground Buildings, Section 907.2.19

    604.2.5 through 604.2.11 {No change.}

    604.2.12 Means of Egress Illumination. Emergency power shall be provided for means of egress illumination in accordance with Sections 1008.3 and 1104.5.1. (90 minutes)

    604.2.13 Membrane Structures. Emergency power shall be provided for exit signs in temporary tents and membrane structures in accordance with Section 3103.12.6.1. (90 minutes) Standby power shall be provided for auxiliary inflation systems in permanent membrane structures in accordance with Section 2702 of the International Building Code. (4 hours) Auxiliary inflation systems shall be provided in temporary air-supported and air-inflated membrane structures in accordance with section 3103.10.4.

    604.2.14 {No change.}

    604.2.15 Smoke Control Systems. Standby power shall be provided for smoke control systems in the following occupancies, or as specified elsewhere in this code, as required in Section 909.11:

    Covered Mall Building, International Building Code, Section 402.7
    Atriums, International Building Code, Section 404.7
    Underground Buildings, International Building Code, Section 405.8
    Group I-3, International Building Code, Section 408.4.2
    Stages, International Building Code, Section 410.3.7.2
    Special Amusement Buildings (as applicable to Group A's), International Building Code, Section 411.1
    Smoke Protected Seating, Section 1029.6.2.1

    604.2.17 Covered and Open Mall Buildings. Emergency power shall be provided in accordance with Section 907.2.20 and 914.2.3.

    604.2.18 Airport Traffic Control Towers. A standby power system shall be provided in airport traffic control towers more than 65 ft. in height. Power shall be provided to the following equipment:

    1. Pressurization equipment, mechanical equipment and lighting.

    2. Elevator operating equipment.

    3. Fire alarm and smoke detection systems.

    604.2.19 Smokeproof Enclosures and Stair Pressurization Alternative. Standby power shall be provided for smokeproof enclosures, stair pressurization alternative and associated automatic fire detection systems as required by the International Building Code, Section 909.20.6.2.

    604.2.20 Elevator Pressurization. Standby power shall be provided for elevator pressurization system as required by the International Building Code, Section 909.21.5.

    604.2.21 Elimination of Smoke Dampers in Shaft Penetrations. Standby power shall be provided when eliminating the smoke dampers in ducts penetrating shafts in accordance with the International Building Code, Section 717.5.3, exception 2.3.

    604.2.22 Common Exhaust Systems for Clothes Dryers. Standby power shall be provided for common exhaust systems for clothes dryers located in multistory structures in accordance with the International Mechanical Code, Section 504.10, Item 7.

    604.2.23 Hydrogen Cutoff Rooms. Standby power shall be provided for mechanical ventilation and gas detection systems of Hydrogen Cutoff Rooms in accordance with the International Building Code, Section 421.8.

    604.2.24 Means of Egress Illumination in Existing Buildings. Emergency power shall be provided for means of egress illumination in accordance with Section 1104.5 when required by the fire code official. (90 minutes in I-2, 60 minutes elsewhere.)

    604.3 through 604.7 {No change.}

    604.8 Energy Time Duration. Unless a time limit is specified by the fire code official, in this chapter or elsewhere in this code, or in any other referenced code or standard, the emergency and standby power system shall be supplied with enough fuel or energy storage capacity for not less than 2-hour full-demand operation of the system.

    Exception: Where the system is supplied with natural gas from a utility provider and is approved.

    (39)

    604.4.2 Written Record ; add the following before last sentence: Current State of Texas Elevator Inspection shall be posted inside elevator.

    (40)

    Section 609.2 ; change to read as follows:

    609.2 Where Required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors, including but not limited to cooking equipment used in fixed, mobile, or temporary concessions, such as trucks, buses, trailers, pavilions, or any form of roofed enclosure, as required by the fire code official.

    Exceptions:

    1. Tents, as provided for in Chapter 31.

    2. {No change to existing Exception.}

    Additionally, fuel gas and power provided for such cooking appliances shall be interlocked with the extinguishing system, as required by Section 904.12.2. Fuel gas containers and piping/hose shall be properly maintained in good working order and in accordance with all applicable regulations.

    (41)

    Section 704.1 ; change to read as follows:

    704.1 Enclosure. Interior vertical shafts including, but not limited to, stairways, elevator hoistways, service and utility shafts, that connect two or more stories of a building shall be enclosed or protected in accordance with the codes in effect at the time of construction but, regardless of when constructed, not less than as required in Chapter 11. New floor openings in existing buildings shall comply with the International Building Code.

    (42)

    Section 807.3 ; change to read as follows:

    807.3 Combustible Decorative Materials. In occupancies in Groups A, E, I, and R-1, and dormitories in Group R-2, curtains, draperies, fabric hangings and other similar combustible decorative materials suspended from walls or ceilings shall comply with Section 807.4 and shall not exceed 10 percent of the specific wall or ceiling area to which they are attached.

    Section 807.5.2.2 and 807.5.2.3 ; change to read as follows:

    807.5.2.2 Artwork in Corridors. Artwork and teaching materials shall be limited on the walls of corridors to not more than 20 percent of the wall area.

    Such materials shall not be continuous from floor to ceiling or wall to wall. Curtains, draperies, wall hangings, and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible.

    Exception: Corridors protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 shall be limited to 50 percent of the wall area.

    807.5.2.3 Artwork in Classrooms. Artwork and teaching materials shall be limited on walls of classrooms to not more than 50 percent of the specific wall area to which they are attached. Curtains, draperies, wall hangings and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible.

    (43)

    Section 807.5.5.2 and 807.5.5.3; change to read as follows:

    807.5.5.2 Artwork in Corridors. Artwork and teaching materials shall be limited on the walls of corridors to not more than 20 percent of the wall area. Such materials shall not be continuous from floor to ceiling or wall to wall. Curtains, draperies, wall hangings and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible.

    Exception: Corridors protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 shall be limited to 50 percent of the wall area.

    807.5.5.3 Artwork in Classrooms. Artwork and teaching materials shall be limited on walls of classrooms to not more than 50 percent of the specific wall area to which they are attached. Curtains, draperies, wall hangings and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible.

    (44)

    901.6 Inspection, Testing and Maintenance: add the following sentence after the first sentence:

    The fire protection alarm, extinguishing systems, and equipment shall be inspected by licensed personnel registered with the State of Texas State Fire Marshal's Office.

    (45)

    Section 901.6.1 ; add Section 901.6.1.1 to read as follows:

    901.6.1.1 Standpipe Testing. Building owners/managers must maintain and test standpipe systems as per NFPA 25 requirements. The following additional requirements shall be applied to the testing that is required every 5 years:

    1. The piping between the Fire Department Connection (FDC) and the standpipe shall be backflushed when foreign material is present, and also hydrostatically tested for all FDC's on any type of standpipe system. Hydrostatic testing shall also be conducted in accordance with NFPA 25 requirements for the different types of standpipe systems.

    2. For any manual (dry or wet) standpipe system not having an automatic water supply capable of flowing water through the standpipe, the tester shall connect hose from a fire hydrant or portable pumping system (as approved by the fire code official) to each FDC, and flow water through the standpipe system to the roof outlet to verify that each inlet connection functions properly. Confirm that there are no open hose valves prior to introducing water into a dry standpipe. There is no required pressure criteria at the outlet. Verify that check valves function properly and that there are no closed control valves on the system.

    3. Any pressure relief, reducing, or control valves shall be tested in accordance with the requirements of NFPA 25. All hose valves shall be exercised.

    4. If the FDC is not already provided with approved caps, the contractor shall install such caps for all FDC's as required by the fire code official.

    5. Upon successful completion of standpipe test, place a blue tag (as per Texas Administrative Code, Fire Sprinkler Rules for Inspection, Test and Maintenance Service (ITM) Tag) at the bottom of each standpipe riser in the building. The tag shall be check-marked as "Fifth Year" for Type of ITM, and the note on the back of the tag shall read "5 Year Standpipe Test" at a minimum.

    6. The procedures required by Texas Administrative Code Fire Sprinkler Rules with regard to Yellow Tags and Red Tags or any deficiencies noted during the testing, including the required notification of the local Authority Having Jurisdiction (fire code official) shall be followed.

    7. Additionally, records of the testing shall be maintained by the owner and contractor, if applicable, as required by the State Rules mentioned above and NFPA 25.

    8. Standpipe system tests where water will be flowed external to the building shall not be conducted during freezing conditions or during the day prior to expected night time freezing conditions.

    9. Contact the fire code official for requests to remove existing fire hose from Class II and III standpipe systems where employees are not trained in the utilization of this firefighting equipment. All standpipe hose valves must remain in place and be provided with an approved cap and chain when approval is given to remove hose by the fire code official.

    (46)

    Section 901.6.3 ; add Section 901.6.3 to read as follows:

    901.6.3 False Alarms and Nuisance Alarms. False alarms and nuisance alarms shall not be given, signaled or transmitted or caused or permitted to be given, signaled or transmitted in any manner.

    (47)

    Section 901.7 ; change to read as follows:

    901.7 Systems Out of Service. Where a required fire protection system is out of service or in the event of an excessive number of activations, the fire department and the fire code official shall be notified immediately and, where required by the fire code official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. ... {Remainder unchanged.}

    (48)

    Section 901.8.2 ; change to read as follows:

    901.8.2 Removal of existing Occupant-use Hose Lines. The fire code official is authorized to permit the removal of occupant-use hose lines and hose valves where all of the following conditions exist:

    1. The hose line(s) would not be utilized by trained personnel or the fire department.

    2. If the occupant-use hose lines are removed, but the hose valves are required to remain as per the fire code official, such shall be compatible with local fire department fittings.

    (49)

    Section 903.1.1 ; change to read as follows:

    903.1.1 Alternative Protection. Alternative automatic fire-extinguishing systems complying with Section 904 shall be permitted in addition to automatic sprinkler protection where recognized by the applicable standard or as approved by the fire code official.

    (50)

    Section 903.2 ; add paragraph to read as follows:

    Automatic Sprinklers shall not be installed in elevator machine rooms, elevator machine spaces, and elevator hoistways, other than pits where such sprinklers would not necessitate shunt trip requirements under any circumstances. Storage shall not be allowed within the elevator machine room. Signage shall be provided at the entry doors to the elevator machine room indicating "ELEVATOR MACHINERY - NO STORAGE ALLOWED."

    (51)

    Section 903.2 ; delete the exception.

    (52)

    903.2.8 (Group R). An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area except for a single structure Group R-l Short Term Rental (STR) occupancy provided that:

    (1)

    The STR and structures comply with all applicable city-adopted codes, regulations, and ordinances including those addressing life safety concerns, and

    (2)

    The total number of guest rooms (rooms designed as bedrooms) shall not exceed five guest rooms, and

    (3)

    No guest rooms shall be located above a second story nor in a basement, and

    (4)

    No more than two guests per room per night shall be permitted, and

    (5)

    The residence is protected by a monitored residential style fire/security system with an appropriate automatic smoke detection system installed throughout the residence with occupant notification devices in accordance with Section 907.5 (Occupant notification systems), and

    (6)

    The residential style fire/security system must be inspected, tested and maintained in accordance with Section 907.8 (Inspection, testing and maintenance), and

    (7)

    Each guest room shall be equipped with a fire extinguisher and fire ladder (if located on the second floor), and

    (8)

    The structure is less than 7,500 square feet, and

    (9)

    The maximum stay for one guest is no more than 30 days, and

    (10)

    The owner of an STR may not rent the STR more than 180 days per year, and

    (11)

    Events may be held at an STR if the STR assembly occupancy area on the ground floor of any structure used as an STR can accommodate the number of event guests per the Fire Code requirement of 15 net square feet of assembly occupancy area per person. The number of people permitted to attend an event will be determined by the Fire Marshal and identified on the Certificate of Occupancy and the Special Use Permit, and

    (12)

    No STR located in a residential zoning district may use a garbage dumpster, and

    (13)

    If located in a residential zone, no advertising signs for the STR are permitted on the premises except for one (1) plaque-style sign mounted on the structure. The plaque shall not exceed four (4) square feet. If the STR is located in a commercial district, signs must comply with the Sign Ordinance related to the zoning district.

    (53)

    Section 903.2.9 ; add Section 903.2.9.3 to read as follows:

    903.2.9.3 Self-Service Storage Facility. An automatic sprinkler system shall be installed throughout all self-service storage facilities.

    (54)

    Section 903.2.11; change 903.2.11.3 and add 903.2.11.7, 903.2.11.8, and 903.2.11.9 as follows:

    903.2.11.3 Buildings 35 feet or more in height. An automatic sprinkler system shall be installed throughout buildings that have one or more stories other than penthouses in compliance with Section 1510 of the International Building Code, located 35 feet (10,668 mm) or more above the lowest level of fire department vehicle access, measured to the finished floor.

    Exception:

    Open parking structures in compliance with Section 406.5 of the International Building Code, having no other occupancies above the subject garage.

    903.2.11.7 High-Piled Combustible Storage. For any building with a clear height exceeding 12 feet (4572 mm), see Chapter 32 to determine if those provisions apply.

    903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be protected by an approved automatic fire-extinguishing system.

    (55)

    Section 903.3.1.1.1 ; change to read as follows:

    903.3.1.1.1 Exempt Locations. When approved by the fire code official, automatic sprinklers shall not be required in the following rooms or areas where such ...{text unchanged}... because it is damp, of fire-resistance-rated construction or contains electrical equipment.

    1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard.

    2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the code official.

    3. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not less than 2 hours.

    4. Elevator machine rooms, machinery spaces, and hoistways, other than pits where such sprinklers would not necessitate shunt trip requirements under any circumstances.

    5. {Delete.}

    (56)

    Section 903.3.1.3 ; change to read as follows:

    903.3.1.3 NFPA 13D Sprinkler Systems. Automatic sprinkler systems installed in one- and two-family dwellings; Group R-3; Group R-4 Condition 1 and townhouses shall be permitted to be installed throughout in accordance with NFPA 13D or in accordance with state law.

    (57)

    Section 903.3.1.4 ; add to read as follows:

    [F] 903.3.1.4 Freeze protection. Freeze protection systems for automatic fire sprinkler systems shall be in accordance with the requirements of the applicable referenced NFPA standard and this section.

    903.3.1.4.1 Attics. Only dry-pipe, preaction, or listed antifreeze automatic fire sprinkler systems shall be allowed to protect attic spaces.

    Exception: Wet-pipe fire sprinkler systems shall be allowed to protect non-ventilated attic spaces where:

    1. The attic sprinklers are supplied by a separate floor control valve assembly to allow ease of draining the attic system without impairing sprinklers throughout the rest of the building, and

    2. Adequate heat shall be provided for freeze protection as per the applicable referenced NFPA standard, and

    3. The attic space is a part of the building's thermal, or heat, envelope, such that insulation is provided at the roof deck, rather than at the ceiling level.

    903.3.1.4.2 Heat trace/insulation. Heat trace/insulation shall only be allowed where approved by the fire code official for small sections of large diameter water-filled pipe.

    (58)

    Section 903.3.5 ; add a second and third paragraph to read as follows:

    [F] Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every water-based fire protection system shall be designed with a 10 psi safety factor. Reference Section 507.4 for additional design requirements.

    All installations in Chapter 9 shall conform to the most recently adopted subdivision regulations found the City of Gainesville Code of Ordinances.

    (59)

    Section 903.4 ; add a second paragraph after the exceptions to read as follows:

    Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering.

    (60)

    Section 903.4.2 ; add second paragraph to read as follows:

    The alarm device required on the exterior of the building shall be a weatherproof horn/strobe notification appliance with a minimum 75 candela strobe rating, installed as close as practicable to the fire department connection and shall be activated only upon sprinkler water flow conditions.

    (61)

    Section 905.2 ; change to read as follows:

    905.2 Installation Standard. Standpipe systems shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psig and a maximum of 40 psig air pressure with a high/low alarm.

    (62)

    Section 905.3 ; add Section 905.3.9 and exception to read as follows:

    905.3.9 Buildings Exceeding 10,000 sq. ft. In buildings exceeding 10,000 square feet in area per story and where any portion of the building's interior area is more than 200 feet (60960 mm) of travel, vertically and horizontally, from the nearest point of fire department vehicle access, Class I automatic wet or manual wet standpipes shall be provided.

    Exceptions:

    1. Automatic dry and semi-automatic dry standpipes are allowed as provided for in NFPA 14.

    2. R-2 occupancies of four stories or less in height having no interior corridors.

    (63)

    Section 905.4, change Item 1, 3, and 5, and add Item 7 to read as follows:

    1. In every required exit stairway, a hose connection shall be provided for each story above and below grade plane. Hose connections shall be located at an intermediate landing between stories, unless otherwise approved by the fire code official.

    2. {No change.}

    3. In every exit passageway, at the entrance from the exit passageway to other areas of a building.

    Exception: Where floor areas adjacent to an exit passageway are reachable from an exit stairway hose connection by a ....{Remainder unchanged.}

    4. {No change.}

    5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), each standpipe shall be provided with a two-way hose connection located to serve the roof or at the highest landing of an exit stairway with stair access to the roof provided in accordance with Section 1011.12.

    6. {No change.}

    7. When required by this Chapter, standpipe connections shall be placed adjacent to all required exits to the structure and at two hundred feet (200') intervals along major corridors thereafter, or as otherwise approved by the fire code official.

    (64)

    Section 905.9 ; add a second paragraph after the exceptions to read as follows:

    Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering.

    (65)

    Section 907.1 ; add Section 907.1.4 and the following paragraph to read as follows:

    907.1.4 Design Standards. Where a new fire alarm system is installed, the devices shall be addressable. Fire alarm systems utilizing more than 20 smoke detectors shall have analog initiating devices.

    All alarm systems new or replacement serving 20 or more alarm actuation devices shall be addressable fire detection systems. Alarm systems serving more than 40 smoke detectors or more than 100 total alarm activating devices shall be analog intelligent addressable fire detection systems. Exception: existing systems need not comply unless the total building remodel or expansion initiated after adoption of this code, as adopted, exceeds 30% of the building. When cumulative building remodel or expansion exceeds 50% of the building, occupant must comply within 18 months of permit application.

    (66)

    Section 907.2.1 ; change to read as follows:

    907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group A occupancies having an occupant load of 300 or more persons or more than 100 persons above or below the lowest level of exit discharge. Group A occupancies not separated from one another in accordance with Section 707.3.10 of the International Building Code shall be considered as a single occupancy for the purposes of applying this section. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy.

    Exception: {No change.}

    Activation of fire alarm notification appliances shall:

    1. Cause illumination of the means of egress with light of not less than 1 foot-candle (11 lux) at the walking surface level, and

    2. Stop any conflicting or confusing sounds and visual distractions.

    (67)

    Section 907.2.3; change to read as follows:

    907.2.3 Group E. A manual fire alarm system that initiates the occupant notification signal utilizing an emergency voice/alarm communication system meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection system shall be installed in Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildings, whether portable buildings or the main building, will be considered one building for alarm occupant load consideration and interconnection of alarm systems.

    Exceptions:

    1. {No change.}

    1.1. Residential In-Home day care with not more than 12 children may use interconnected single station detectors in all habitable rooms. (For care of more than five children 2 1/2 or less years of age, see Section 907.2.6.) {No change to remainder of exceptions.}

    (68)

    Section 907.2.13 , Exception 3; change to read as follows:

    3. Open air portions of buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code; however, this exception does not apply to accessory uses including but not limited to sky boxes, restaurants, and similarly enclosed areas.

    (69)

    Section 907.4.2 ; add Section 907.4.2.7 to read as follows:

    907.4.2.7 Type. Manual alarm initiating devices shall be an approved double action type.

    (70)

    Section 907.6.1 ; add Section 907.6.1.1 to read as follows:

    907.6.1.1 Wiring Installation. All fire alarm systems shall be installed in such a manner that a failure of any single initiating device or single open in an initiating circuit conductor will not interfere with the normal operation of other such devices. All signaling line circuits (SLC) shall be installed in such a way that a single open will not interfere with the operation of any addressable devices (Class A). Outgoing and return SLC conductors shall be installed in accordance with NFPA 72 requirements for Class A circuits and shall have a minimum of four feet separation horizontal and one-foot vertical between supply and return circuit conductors. The initiating device circuit (IDC) from a signaling line circuit interface device may be wired Class B, provided the distance from the interface device to the initiating device is ten feet or less.

    (71)

    Section 907.6.3 ; delete all four Exceptions.

    (72)

    Section 907.6.6 ; add sentence at end of paragraph to read as follows:

    [F] See 907.6.3 for the required information transmitted to the supervising station.

    (73)

    907.7 Installation: Add second paragraph to read - All fire alarm systems shall be installed in such a manner that a failure of any single initiating device or single open in an initiating circuit conductor will not interfere with the normal operation of other such devices. All signaling line circuits (SLC) shall be installed in such a way that a single open will not interfere with the operation of any addressable devices (Class A). Outgoing and return SLC conductors shall be installed in accordance with NFPA 72 requirements for Class A circuits and shall have a minimum of four feet separation horizontal and one-foot vertical between supply and return circuit conductors. The initiating device circuit (IDC) from a signaling line circuit interface device may be wired Class B, provided the distance from the interface device to the initiating device is ten feet or less.

    (74)

    Section 909.22; add to read as follows:

    909.22 Stairway or Ramp Pressurization Alternative. Where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and the stair pressurization alternative is chosen for compliance with Building Code requirements for a smokeproof enclosure, interior exit stairways or ramps shall be pressurized to a minimum of 0.10 inches of water (25 Pa) and a maximum of 0.35 inches of water (87 Pa) in the shaft relative to the building measured with all interior exit stairway and ramp doors closed under maximum anticipated conditions of stack effect and wind effect. Such systems shall comply with Section 909, including the installation of a separate fire-fighter's smoke control panel as per Section 909.16, and a Smoke Control Permit shall be required from the fire department as per Section 105.7.

    [F] 909.22.1 Ventilating equipment. The activation of ventilating equipment for the stair or ramp pressurization system shall be by smoke detectors installed at each floor level at an approved location at the entrance to the smokeproof enclosure. When the closing device for the stairway or ramp shaft and vestibule doors is activated by smoke detection or power failure, the mechanical equipment shall activate and operate at the required performance levels. Smoke detectors shall be installed in accordance with Section 907.3.

    909.22.1.1 Ventilation Systems. Smokeproof enclosure ventilation systems shall be independent of other building ventilation systems. The equipment, control wiring, power wiring and ductwork shall comply with one of the following:

    1. Equipment, control wiring, power wiring and ductwork shall be located exterior to the building and directly connected to the smokeproof enclosure or connected to the smokeproof enclosure by ductwork enclosed by not less than 2-hour fire barriers constructed in accordance with Section 707 of the Building Code or horizontal assemblies constructed in accordance with Section 711 of the Building Code, or both.

    2. Equipment, control wiring, power wiring and ductwork shall be located within the smokeproof enclosure with intake or exhaust directly from and to the outside or through ductwork enclosed by not less than 2-hour barriers constructed in accordance with Section 707 of the Building Code or horizontal assemblies constructed in accordance with Section 711 of the Building Code, or both.

    3. Equipment, control wiring, power wiring and ductwork shall be located within the building if separated from the remainder of the building, including other mechanical equipment, by not less than 2-hour fire barriers constructed in accordance with Section 707 of the Building Code or horizontal assemblies constructed in accordance with Section 711 of the Building Code, or both.

    Exceptions:

    1. Control wiring and power wiring utilizing a 2-hour rated cable or cable system.

    2. Where encased with not less than 2 inches (51 mm) of concrete.

    3. Control wiring and power wiring protected by a listed electrical circuit protective systems with a fire-resistance rating of not less than 2 hours.

    909.21.1.2 Standby Power. Mechanical vestibule and stairway and ramp shaft ventilation systems and automatic fire detection systems shall be provided with standby power in accordance with Section 2702 of the Building Code.

    909.22.1.3 Acceptance and Testing. Before the mechanical equipment is approved, the system shall be tested in the presence of the fire code official to confirm that the system is operating in compliance with these requirements.

    (75)

    Section 910.2 ; change Exception 2. and 3.to read as follows:

    [F] 2. Only manual smoke and heat removal shall not be required in areas of buildings equipped with early suppression fast-response (ESFR) sprinklers. Automatic smoke and heat removal is prohibited.

    3. Only manual smoke and heat removal shall not be required in areas of buildings equipped with control mode special application sprinklers with a response time index of 50(m*S)1/2 or less that are listed to control a fire in stored commodities with 12 or fewer sprinklers. Automatic smoke and heat removal is prohibited.

    (76)

    Section 910.2 ; add subsections 910.2.3 with exceptions to read as follows:

    910.2.3 Group H . Buildings and portions thereof used as a Group H occupancy as follows:

    1. In occupancies classified as Group H-2 or H-3, any of which are more than 15,000 square feet (1394 m2) in single floor area.

    Exception: Buildings of noncombustible construction containing only noncombustible materials.

    2. In areas of buildings in Group H used for storing Class 2, 3, and 4 liquid and solid oxidizers, Class 1 and unclassified detonable organic peroxides, Class 3 and 4 unstable (reactive) materials, or Class 2 or 3 water-reactive materials as required for a high-hazard commodity classification.

    Exception: Buildings of noncombustible construction containing only noncombustible materials.

    (77)

    Section 910.3 ; add section 910.3.4 to read as follows:

    910.3.4 Vent Operations. Smoke and heat vents shall be capable of being operated by approved automatic and manual means. Automatic operation of smoke and heat vents shall conform to the provisions of Sections 910.3.2.1 through 910.3.2.3.

    [F] 910.3.4.1 Sprinklered buildings. Where installed in buildings equipped with an approved automatic sprinkler system, smoke and heat vents shall be designed to operate automatically. The automatic operating mechanism of the smoke and heat vents shall operate at a temperature rating at least 100 degrees F (approximately 38 degrees Celsius) greater than the temperature rating of the sprinklers installed.

    Exception: Manual only systems per Section 910.2.

    910.3.4.2 Nonsprinklered Buildings. Where installed in buildings not equipped with an approved automatic sprinkler system, smoke and heat vents shall operate automatically by actuation of a heat-responsive device rated at between 100°F (56°C) and 220°F (122°C) above ambient.

    Exception: Listed gravity-operated drop out vents.

    (78)

    Section 910.4.3.1 ; change to read as follows:

    910.4.3.1 Makeup Air. Makeup air openings shall be provided within 6 feet (1829 mm) of the floor level. Operation of makeup air openings shall be automatic. The minimum gross area of makeup air inlets shall be 8 square feet per 1,000 cubic feet per minute (0.74 m2 per 0.4719 m3/s) of smoke exhaust.

    (79)

    Section 910.4.4 ; change to read as follows:

    910.4.4 Activation. The mechanical smoke removal system shall be activated automatically by the automatic sprinkler system or by an approved fire detection system. Individual manual controls shall also be provided.

    Exception: Manual only systems per Section 910.2.

    (80)

    Section 912.2 ; add Section 912.2.3 to read as follows:

    912.2.3 Hydrant Distance. An approved fire hydrant shall be located within 100 feet of the fire department connection as the fire hose lays along an unobstructed path.

    (81)

    Section 913.2.1 ; add second paragraph and exception to read as follows:

    When located on the ground level at an exterior wall, the fire pump room shall be provided with an exterior fire department access door that is not less than 3 ft. in width and 6 ft. - 8 in. in height, regardless of any interior doors that are provided. A key box shall be provided at this door, as required by Section 506.1.

    Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior wall, the corridor leading to the fire pump room access from the exterior of the building shall be provided with equivalent fire resistance as that required for the pump room, or as approved by the fire code official. Access keys shall be provided in the key box as required by Section 506.1.

    (82)

    Section 914.3.1.2 ; change to read as follows:

    914.3.1.2 Water Supply to required Fire Pumps. In buildings that are more than 120 feet (36.58 m) in building height, required fire pumps shall be supplied by connections to no fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate.

    Exception: {No change to exception.}

    (83)

    Section 1006.2.2.6 ; add a new Section 1006.2.2.6 as follows:

    1006.2.2.6 Electrical Rooms. For electrical rooms, special exiting requirements may apply. Reference the Electrical Code as adopted.

    (84)

    Section 1009.1 ; add the following Exception 4:

    Exceptions:

    {previous exceptions unchanged}

    4. Buildings regulated under State Law and built in accordance with State registered plans, including any variances or waivers granted by the State, shall be deemed to be in compliance with the requirements of Section 1009.

    (85)

    Section 1010.1.9.4 Bolt Locks ; change Exceptions 3 and 4 to read as follows:

    Exceptions:

    3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, M or S occupancy. {Remainder unchanged.}

    4. Where a pair of doors serves a Group A, B, F, M or S occupancy {Remainder unchanged.}

    (86)

    Section 1015.8 Window Openings; change number 1 to read as follows:

    1. Operable windows where the top of the sill of the opening is located more than 55 ft (16,764 mm) above the finished grade or other surface below and that are provided with window fall prevention devices that comply with ASTM F 2006.

    (87)

    Section 1020.1 Construction; add Exception 6 to read as follows:

    6. In group B occupancies, corridor walls and ceilings need not be of fire-resistive construction within a single tenant space when the space is equipped with approved automatic smoke-detection within the corridor. The actuation of any detector shall activate self-annunciating alarms audible in all areas within the corridor. Smoke detectors shall be connected to an approved automatic fire alarm system where such system is provided.

    (88)

    Section 1029.1.1.1 Spaces under Grandstands and Bleachers ; delete this section.

    (89)

    Section 1031.2 ; change to read as follows:

    1031.2 Reliability. Required exit accesses, exits and exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency exit or exit passageway shall not be used for any purpose that interferes with a means of egress.

    (90)

    Section 1103.3 ; add sentence to end of paragraph as follows:

    Provide emergency signage as required by Section 607.3.

    (91)

    Section 1103.5 ; add Section 1103.5.1 to read as follows:

    1103.5.1 Spray Booths and Rooms. Existing spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system in accordance with Section 2404.

    (92)

    Section 1103.7 ; add Section 1103.7.8 and 1103.7.8.1 to read as follows:

    1103.7.8 Fire Alarm System Design Standards. Where an existing fire alarm system is upgraded or replaced, the devices shall be addressable. Fire alarm systems utilizing more than 20 smoke and/or heat detectors shall have analog initiating devices.

    Exception: Existing systems need not comply unless the total building, or fire alarm system, remodel or expansion exceeds 30% of the building. When cumulative building, or fire alarm system, remodel or expansion initiated after the date of original fire alarm panel installation exceeds 50% of the building, or fire alarm system, the fire alarm system must comply within 18 months of permit North Central Texas Council of Governments 26 As of August 2015 IFC Amendments application.

    1103.7.8.1 Communication requirements. Refer to Section 907.6.6 for applicable requirements.

    (93)

    Section 2304.1 ; change to read as follows:

    2304.1 Supervision of Dispensing. The dispensing of fuel at motor fuel-dispensing facilities shall be in accordance with the following:

    1. Conducted by a qualified attendant; and/or,

    2. Shall be under the supervision of a qualified attendant; and/or

    3. Shall be an unattended self-service facility in accordance with Section 2304.3.

    At any time the qualified attendant of item Number 1 or 2 above is not present, such operations shall be considered as an unattended self-service facility and shall also comply with Section 2304.3.

    (94)

    Section 2401.2 ; delete this section. [Reason: inadequate coverage with Chapter 15.]

    (95)

    Table 3206.2, footnote j ; change text to read as follows:

    j. Where storage areas are protected by either early suppression fast response (ESFR) sprinkler systems or control mode special application sprinklers with a response time index of 50 (m • s) 1/2 or less that are listed to control a fire in the stored commodities with 12 or fewer sprinklers, installed in accordance with NFPA 13, manual smoke and heat vents or manually activated engineered mechanical smoke exhaust systems shall be required within these areas.

    (96)

    Section 3310.1 ; add sentence to end of paragraph to read as follows:

    When fire apparatus access roads are required to be installed for any structure or development, they shall be approved prior to the time at which construction has progressed beyond completion of the foundation of any structure.

    (97)

    Section 5601.1.3 ; change to read as follows:

    5601.1.3 Fireworks. The possession, manufacture, storage, sale, handling, and use of fireworks are prohibited.

    Exceptions:

    1. Only when approved for fireworks displays, storage, and handling of fireworks as allowed in Section 5604 and 5608.

    2. The use of fireworks for approved fireworks displays as allowed in Section 5608.

    (98)

    Section 5703.6 ; add a sentence to read as follows:

    5703.6 Piping Systems. Piping systems, and their component parts, for flammable and combustible liquids shall be in accordance with Sections 5703.6.1 through 5703.6.11. An approved method of secondary containment shall be provided for underground tank and piping systems.

    (99)

    Section 5704.2.9.5 ; change Section 5704.2.9.5 and add Section 5704.2.9.5.3 to read as follows:

    5704.2.9.5 Above-ground Tanks Inside of Buildings. Above-ground tanks inside of buildings shall comply with Section 5704.2.9.5.1 through 5704.2.9.5.3.

    5704.2.9.5.1 {No change.}

    5704.2.9.5.2 {No change.}

    5704.2.9.5.3 Combustible Liquid Storage Tanks Inside of Buildings. The maximum aggregate allowable quantity limit shall be 3,000 gallons (11 356 L) of Class II or III combustible liquid for storage in protected aboveground tanks complying with Section 5704.2.9.7 when all of the following conditions are met:

    1. The entire 3,000-gallon (11 356 L) quantity shall be stored in protected above-ground tanks;

    2. The 3,000 gallon (11 356 L) capacity shall be permitted to be stored in a single tank or multiple smaller tanks;

    3. The tanks shall be located in a room protected by an automatic sprinkler system complying with Section 903.3.1.1; and

    4. Tanks shall be connected to fuel-burning equipment, including generators, utilizing an approved closed piping system.

    The quantity of combustible liquid stored in tanks complying with this section shall not be counted towards the maximum allowable quantity set forth in Table 5003.1.1(1), and such tanks shall not be required to be located in a control area. Such tanks shall not be located more than two stories below grade.

    (100)

    Section 5704.2.11.4 ; add a sentence to read as follows:

    5704.2.11.4 Leak Prevention. Leak prevention for underground tanks shall comply with Sections 5704.2.11.4.1 through 5704.2.11.4.3. An approved method of secondary containment shall be provided for underground tank and piping systems.

    (101)

    Section 5704.2.11.4.2 ; change to read as follows:

    5704.2.11.4.2 Leak Detection. Underground storage tank systems shall be provided with an approved method of leak detection from any component of the system that is designed and installed in accordance with NFPA 30 and as specified in Section 5704.2.11.4.3.

    (102)

    Section 5704.2.11.4 ; add Section 5704.2.11.4.3 to read as follows:

    5704.2.11.4.3 Observation Wells. Approved sampling tubes of a minimum 4 inches in diameter shall be installed in the backfill material of each underground flammable or combustible liquid storage tank. The tubes shall extend from a point 12 inches below the average grade of the excavation to ground level and shall be provided with suitable surface access caps. Each tank site shall provide a sampling tube at the corners of the excavation with a minimum of 4 tubes. Sampling tubes shall be placed in the product line excavation within 10 feet of the tank excavation and one every 50 feet routed along product lines towards the dispensers, a minimum of two are required.

    (103)

    Section 6103.2.1 ; add Section 6103.2.1.8 to read as follows:

    6103.2.1.8 Jewelry Repair, Dental Labs and Similar Occupancies. Where natural gas service is not available, portable LP-Gas containers are allowed to be used to supply approved torch assemblies or similar appliances. Such containers shall not exceed 20-pound (9.0 kg) water capacity. Aggregate capacity shall not exceed 60-pound (27.2 kg) water capacity. Each device shall be separated from other containers by a distance of not less than 20 feet.

    (104)

    Section 6104.2 , Exception; add an exception 2 to read as follows:

    Exceptions:

    1. {existing text unchanged}

    2. Except as permitted in Sections 308 and 6104.3.2, LP-gas containers are not permitted in residential areas.

    (105)

    Section 6104.3 ; add Section 6104.3.2 to read as follows:

    6104.3.2 Spas, Pool Heaters, and Other Listed Devices. Where natural gas service is not available, an LP-gas container is allowed to be used to supply spa and pool heaters or other listed devices. Such container shall not exceed 250-gallon water capacity per lot. See Table 6104.3 for location of containers.

    Exception: Lots where LP-gas can be off-loaded wholly on the property where the tank is located may install up to 500-gallon above ground or 1,000 gallon underground approved containers.

    (106)

    Section 6107.4 and 6109.13 ; change to read as follows:

    6107.4 Protecting Containers from Vehicles. Where exposed to vehicular damage due to proximity to alleys, driveways or parking areas, LP-gas containers, regulators and piping shall be protected in accordance with Section 312.

    6109.13 Protection of Containers. LP-gas containers shall be stored within a suitable enclosure or otherwise protected against tampering. Vehicle impact protection shall be provided as required by Section 6107.4.

    (107)

    Appendix A; A101.1 Scope ; add the following to the end of the sentence:

    All references to the "Board of Appeals" shall mean the "City of Gainesville Board of Appeals" and their adopted regulations.

    (108)

    Table B105.2 ; change footnote a. to read as follows:

    a. The reduced fire-flow shall be not less than 1,500 gallons per minute.

(Ord. No. 1401-12-2016, § 4, 12-20-16; Ord. No. 1429-03-2018, §§ 4, 5, 3-20-18)